SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
PEAKCURRENT
PEAKPOWER Note.6
OUTPUT
VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.7
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGTEMP. Note.5
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
DCOKREALY CONTACTRATINGS(max.)
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
ACCURRENT (Typ.)
1500ms,150ms/230VAC 3000ms,150ms/115VACatfullload
14ms/230VACatfullload
90~264VAC127~370VDC
47~63Hz
94%
0.94/230VAC0.99/115VACatfullload
5A/115VAC2.5A/230VAC
56~65V
40A/115VAC80A/230VAC
<0.8mA /240VAC
29~33V
Protectiontype:Shutdowno/pvoltage withauto-recoveryorre-powerontorecovery
105 5 (TSW:detectonheatsinkofpowerswitch)
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
UL508 TUVEN60950-1approved,
CompliancetoEN55022(CISPR22)ClassB
CompliancetoEN61000-3-2,-3
-25~+70 (Refertooutputloadderatingcurve)
60Vdc/0.3A,30Vdc/1A,30Vac/0.5A resistiveload
20~95%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
Component:10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
112.9Khrsmin.MIL-HDBK-217F(25 )
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2),EN61204-3,heavyindustrylevel,
criteria A ,SEMIF47approved
85.5*125.2*128.5mm(W*H*D)
1.6Kg;8pcs/13.8Kg/0.9CUFT
POWERFACTOR (Typ.)
SDR-480-48
48V
10A
0~10A
480W
15A
120mVp-p
48~55V
1.0%
0.5%
1.0%
SDR-480-24
24V
20A
0~20A
480W
30A
720W(3sec.)
100mVp-p
24~28V
1.2%
0.5%
1.0%
Features :
SDR-480 series
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC O/P-DCOK:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:>100MOhms/500VDC/25 /70%RH
EMICONDUCTION&RADIATION
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note4)
PROTECTION
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
480WSingleOutputIndustrialDINRAIL withPFCFunction
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.94
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
Built-in DC OK relay contact
150% peak load capability
FileName:SDR-480-SPEC2009-04-22
Normallyw morethan3 andthenshutdowno/pvoltagewithauto-recoveryorkswithin110~150%ratedoutputpowerfor seconds
>150%ratedpower,constantcurrentlimitingwithauto-recoverywithin2secondsandmaycausetoshutdownifover2seconds
PQ