DR-75 Series-0106 1/2
I Fealures :
Universal AC input/Full range
P rotection s: Short circu it/Over I oad/Ove r voltag e/Over tem pe ratu re
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 1 5
UL 508(industrial control equipment)approved
LED indicator for power on
100%full load burn-in test
Fix switching frequency at 50KHz
3 years warranty
SPECIFICATION
c(y^US
CBC€
MODEL DR-7S-12 DR-7S-24 DR-7S-4&
DC VOLTAGE 12V 24V 4fiV
RATED CURRENT 6.aA 3.2A 1.6A
CURRENT RANGE Û-6.âA Û-32A 0 -1 6A
RATED POWER 76W 76.6 W 76. ew
RIPPLE* NOISE (max.) Notei lÛÛfnVpp 150mVp-p 240mVpp
OUTPUT VOLTAGE ADJ. RANGE 12- 14V 24 - 26V 46- 53V
VOLTAGE TOLERANCE Note.î +2.0% ±1.0% +1.0%
LINE REGULATION =0.6% ±0.5% =0.5%
LOAD REGULATION +1.0% ±1.0% +1.0%
SETUP, RISE TIME 1000 ms, 60 ms/230VAC 1 fiOO ms, 60 ms/116VAC at f jI I load
HOLDTIME[Typ,J 60ms/23CVAC 12ms/115VAC at fui 1 load
VOLTAGE RANGE 65-264VAC 120-370VDC
FREQUENCY RANGE 47-63HZ
INPUT
EFFICIENCY[Typ.) 76% 60% 61%
AC CURRENT [Typ.J 1.6A/115V 0.96A/23ÛV
INRUSH CURRENT (Typ.) CQLDSTART20W11SVAC 4ÛA;23ÛVAC
LEAKAGE CURRENT <1mA/240VAC
OVERLOAD
105- 160% ratedoutput power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
PROTECTIONOVERVOLTAGE
15- 16.5V 29-34V 56 - 65V
Protection type : Hiccup mode, recovers automatically afterfault condition is rerrüved
OVER TEMPERATURE
(TSW1J Detect on beat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKINGTEMP.
-10 - +60 C ( Refe r to outp ut load derat ing curve)
WORKING HUMIDITY
20 - 90% RH non-condensi ng
EU\^RONMEMT
STORAGE TEMP, HUMIDITY
-20-+65C, 10-95%RH
TEMP. COEFFICIENT
+0.03%i'C(0-b0'C)
VIBRATION 10 - EtìOHz, 2G 10min./1 cycle, period for 60min. each along X, Y, Zaxes
SAFETY STANDARDS
UL506JUVEN6Û95Û-1 Approved
SAFETY &
WITHSTAND VOLTAGE l/P-0.'P:3KVAC l.'P-FG:1,5KVAC O.'P-FG;0.5KVAC
ISOLATION RESISTANCE
l/P-O/P, l.'P-FG, 0.'P-FG:1ÛÛM Ohms/500VDC
EMC
(Note 4|
EHICONDUCTIONS.RADIATION Compliance to EN 55011,EN 55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMSIMMUNITY
Compliance to EN61000-4-2,3,4,5,6.6,11, ENV50204, EN55Û24, EN61000-6^ (EN50062-2) Heavy irriustry level, criteria A
MTBF
123.1Khrs min. MIL-HDBK-217F(25“C)
OTHERS DIMENSION
55.6*125.2*1 ÛÛmm (W*H*D)
PACKING
0.6Kg;20pcs/13Kgi1.1CUFT
NOTE
1. All parameters NOT specialty mentioned are measured at 230VAC input, rated load and 250 of ambient temperature.
2. Ripple * noise are measured al 20MHz oi bandwidth by using a 12" twisted pair-wire terminated witn a 0.1 uf & 47uf parallel capacitor.
3. Tolerance; includes set up tolerance, liine regulation and load regulation.
4. The power supply is considered acomponent which will be installed into a tinal equipment. The final equipment must be reHDonfirmed that it still meets
EMC directives.
International Headquarters: 707 Dayton Road PO Box 1040 Ottawa, IL 61350 USA
815-433-5100 Fax 433-5104
European Headquarters: Westlink Commercial Park Oranmore Co. Galway Ireland
+353 91 792444 F
ax
+353 91 792445 www.bb-europe.com [email protected] [email protected]