Features
Distributed DA&C Systems
All product specifications are subject to change without notice Last updated : 20-Jan-2006
ADAM-5000/485
ADAM-5000E
Introduction
The ADAM-5000/485 and ADAM-5000E systems use the EIA RS-485 communication protocol. This is the industry's most widely used, balanced, bidirectional transmission line
standard. RS-485 was specifically developed for industrial applications to transmit and receive data at high rates over long distances.
Specifications
Control System
CPU 16-bit 80188 microprocessor
I/O Slots ADAM-5000/485: 4
ADAM-5000E: 8
LED Indicators Power, CPU, communications
Watchdog Timer 1.6 sec. (System)
Communications
Command Format ASCII command/response protocol, Modbus/RTU
Communication RS-485: 1.2 km (4000 feet)
Distance
Data Format Asynchronous. 1 start bit, 8 data bits, 1 stop bit, no
parity
Network Protocols Programming link: RS-232 (3-wire: TX, RX, GND)
Communication: RS-485 (2-wire)
Reliability Check Communication error checking with checksum
Max. Nodes 256 (in RS-485 daisy-chain network)
Speeds (kbps) 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, and 115.2
Power
Power Consumption 1.0 W (ADAM-5000/485) (not including I/O modules)
4.0 W (ADAM-5000E) (not including I/O modules)
Power Input Unregulated 10 ~ 30 V
DC
Software
Driver Support Windows DLL, OPC server, Wonderware
®
InTouch
®
,
Intellution
®
, iFIX
®
, Citect.
Protection
Communication Line 2500 V
DC
(ADAM-5000/485)
Isolation 3000 V
DC
(ADAM-5000E)
Communication Power 3000 V
DC
Isolation
I/O Module Isolation 3000 V
DC
Transient Protection RS-485 communication lines, power input
Power Reversal Yes
Protection
General
Certifications CE, FM
Connectors 1 x DB9-M/DB9-F/screw terminal for RS-485
(communication)
1 x DB9-F for RS-232 (configuration)
1 x Screw-terminal for power input
Dimensions (WxHxD) 4-slot: 231 x 110 x 75 mm
8-slot: 355 x 110 x 75 mm
Enclosure ABS+PC
Mounting DIN 35 rail, wall, rack (with mounting kit)
Environment
Humidity 5 ~ 95%, non-condensing
Operating Temperature -10 ~ 70° C (14 ~ 158° F)
Storing Temperature -25 ~ 85° C (-13 ~ 185° F)
Ordering Information
ADAM-5000/485 Distributed DA&C System Based on RS-485 (4 slot)
ADAM-5000E Distributed DA&C System Based on RS-485 (8 slot)
PCLS-OPC/ADM OPC Server for ADAM-4000/5000 Series (RS-485)
PCLS-OCX ActiveX Control for Data Acquisition and Control
PCLS-ADAMVIEW32 ADAMView Data Acquisition Software
RS-485 Communication for easy installation and networking
4 or 8 slots for up to 128 points data monitoning card control in one
module
Extensive Software support, inclucles windows DLL drivers, OCX drivers,
OPC server and popular HMI/SCADA software drivers.
Seamlessly inteqrated with easy-to-use ADAMView data acquisition
software.
4-Slot Distributed DA&C System
for RS-485 Networks
8-Slot Distributed DA&C System
for RS-485 Networks